Description
Genset Controls at your fingertips
There is no comfort like being in command. Kirloskar Green Gensets put the command in your hands. Micro-processor-based Genset controllers display a host of Genset parameters and put all controls at your fingertips.
Monitoring Features
- Lube oil Pressure, Engine Temperature, RPM, lube oil Temperature*
- Run Hours, No. of starts, Fuel Level, Auto / Manual Stop, BaMery charge condition, AC Phase Voltage, Current, kVA, kW, kWh, kVAr, Power Factor
Optional Features
- Modbus communication*
* Features are available from 15 kVA onwards
Diagnostic Features
- Ballery charging failure, Over speed, Under speed, Over Current, Under Voltage, Over Voltage, Over kW, Phase Sequence monitoring, Phase missing, Common Alarm, Hooter output
- Low lube oil Pressure, High Engine Temperature, Low/High battery voltage, Low Fuel Level alarm, Over Crank protection, Routine Maintenance indicator, Genset Test Facility, fail to start/stop
Product Specifications
Prime Rating at rated rpm ( as per ISO8528)1 |
kVA | 160 | 180 | 200 | 250 | ||
kW | 128 | 144 | 160 | 200 | |||
Genset Model |
KG1-160WS | KG1-180WS | KG1-200WS | KG1-1-250WS | |||
Frequency |
Hz | 50 | 50 | 50 | 50 | ||
Power factor |
lagging | 0.8 | 0.8 | 0.8 | 0.8 | ||
Voltage |
V | 415 3Ø | 415 3Ø | 415 3Ø | 415 3Ø | ||
Governing class (As per ISO 8528 Part-V) |
G3 | G3 | G3 | G3 | |||
Noise level |
dBA | < 75 | < 75 | < 75 | < 75 | ||
Fuel Consumption* |
At 100% Load | Ltrs/hr | 36.6 | 41.3 | 45.9 | 56.9 | |
At 75% Load | 27.7 | 30.9 | 34.4 | 42.6 | |||
At 50% Load | 19.1 | 22.7 | 25.5 | 22.9 | |||
Fuel tank capacity |
Ltrs | 300 | 460 | 460 | 460 | ||
Weight of genset with canopy (approx..)^ |
Dry | Kg | 2730 | 3900 | 3900 | 4010 | |
Wet | Kg | 3010 | 4300 | 4340 | 4320 | ||
Overall dimensions of genset^ |
Length | mm | 4000 | 4300 | 4340 | 4340 | |
Width | mm | 1500 | 1740 | 1740 | 1740 | ||
Height | mm | 1915 | 1970 | 1970 | 1975 | ||
Electrical Battery starting voltage |
Volts-DC | 12 | 24 | 24 | 24 | ||
ENGINE |
|||||||
Engine Model |
6K1080TA G2 | GSL1500TA G2 | GSL1500TA G2 | GSL1500TA G3 | |||
Rated output (Prime Continuous rating as per ISO 8528-1) |
KW | 147 | 183 | 183 | 228 | ||
HP | 200 | 248 | 248 | 310 | |||
No. of cylinder |
Number | 6 | 6 | 6 | 6 | ||
Cubic capacity |
Ltrs | 6.48 | 8.86 | 8.86 | 8.86 | ||
Bore x Stroke |
mm | 150 x 125 | 118 x 135 | 118 x 135 | 118 x 135 | ||
Rated Speed |
RPM | 1500 | 1500 | 1500 | 1500 | ||
Aspiration |
NA/TC/TA | TA | TA | TA | TA | ||
Lube Oil change period |
Hrs | 500 | 500 | 500 | 500 | ||
Lube Oil Sump Capacity |
Ltrs | 18 | 27 | 27 | 27 | ||
Coolant Capacity |
Ltrs | 28 | 32 | 29.2 | 31.8 | ||
ALTERNATOR |
|||||||
Insulation Class |
Class H | ||||||
Ingression Protection |
IP 23 | ||||||
Alternator Efficiency (at 100% load) 0.8 pf** |
93 | 93 | 93.5 | 93.6 | |||
Alternator Efficiency (at 75% load) 0.8 pf** |
93.3 | 93.6 | 93.8 | 93.9 | |||
Permissible Voltage Dip at Full Load 0.8 pf |
< 20% | < 20% | < 20% | < 19% | |||
Time Permitted to build up rated voltage at Rated RPM |
< 1 sec provided engine reach the rated speed | ||||||
Short Circuit Ratio |
0.518 | 0.53 | 0.545 | 0.45 | |||
Short Circuit Withstand Time |
sec | 3 times rated current for < 3sec | |||||
Overload Withstand Capacity |
% | 10% overload for one hour once in 12 hours & for 150% for 30 sec |